Performance Chart

The Performance Chart below is divided into two sections to help you evaluate the overall performance of the systems. The System Performance Criteria are the most important to consider because they represent the performance in a typical installation.

SYSTEM PERFORMANCE CRITERIA (Tested on Actual Understructure)
Panel U/S SYSTEM WEIGHT
(lbs/ft²)
STATIC LOADS ROLLING LOADS IMPACT LOADS
(lbs)
Design Loads*
(lbs)
Safety Factors*
(min 2.0)
10 Passes
(lbs)
10,000 Passes
(lbs)
WC5000 Cornerlock 6.9 1000 PASS 1000 700 150
WC5000 Snap-Tite/
Bolt-Tite
7.4 1000 PASS 1000 700 150
WC5000 Heavy Duty 7.6 1250 PASS 1200 875 150
WC6000 Heavy Duty

8.28

1500

PASS

1500

1050

150